C1, C2, C3 and FI: what the codes on an EICR mean

Four codes decide how a condition report reads. Under the A4:2026 model forms only two of them make the report unsatisfactory.

By the Tradear team · · 3 min read

Each observation on an Electrical Installation Condition Report carries a classification code. The code tells the person who ordered the report how serious the problem is and how quickly to act.

  • C1: danger present. There is a risk of injury and immediate remedial action is needed. Electricians will usually make it safe there and then, with the client's agreement.
  • C2: potentially dangerous. Urgent remedial action is needed.
  • C3: improvement recommended. Not dangerous as found, but it would bring the installation closer to the current standard.
  • FI: further investigation required without delay. Something the inspector could not fully check may hide a problem.

Satisfactory or unsatisfactory

The model EICR for BS 7671:2018+A4:2026 lists C1 and C2 observations separately from C3 and FI. Any C1 or C2 makes the overall condition unsatisfactory. C3 and FI observations are recorded in their own list and do not, on their own, change the overall result.

That does not make an FI optional. For a rented home in England, the landlord rules treat further investigation like remedial work: it has to be done within 28 days or the time the report gives.

Writing observations people can act on

  • Say where it is: the board, the circuit and the room.
  • Say what is wrong in words a landlord or homeowner understands.
  • Link it to the schedule item it came from, so the code and the checklist agree.
  • Attach a photo where it helps. The A4 form notes that photographs and thermal images can be attached.