BS 7671:2018+A4:2026 was published on 15 April 2026, with new model forms in Appendix 6. The earlier amendment was withdrawn on 15 October 2026, so new certificates and reports should now be completed to A4.

On the condition report (EICR)

  • Observations are split: C1 and C2 in one list, which decide the overall result; C3 and FI in another, which are advisory.
  • Earthing arrangements now separate TN-C-S (PME) from TN-C-S (PNB).
  • New boxes for maximum demand, breaking capacities, the main switch device and its settings, and RCD type (AC, A, F or B).
  • The circuit schedule gains a line for an RCD protecting the whole board.
  • The inspection schedule adds an item for arc fault detection devices (AFDDs).
  • Standard limitation wording now says that safety alerts and product recalls were not checked.
  • Premises types are residential, commercial, industrial or other.

Why it matters for your software

Certificates produced by apps are expected to carry the content of the model forms, not copy their design. If your current app still prints the A2 layout, check when it will be updated. Tradear's certificates follow the A4 content from the start.